VTScada Driver Library
Devices that have been used with VTScada*
|
Manufacturer |
Model(s) |
Protocol |
Notes |
|---|---|---|---|
|
ABB |
Variable Speed Drives, AC500 Series PLCs |
Modbus |
|
|
TotalFlow Family |
Enron Modbus |
|
|
|
AC500 Series PLCs |
IEC-60870-104 |
|
|
|
Allen-Bradley® |
SLC 500, PLC-2, PLC-3, PLC-5, PLC-5-250 (Pyramid Integrator), Micrologix, CompactLogix®, ControlLogix® |
DF1 |
MicroLogix 1400 can also be configured to DNP3. |
|
Ethernet/IP |
|
||
|
Micro800 Programmable Controllers |
Symbolic CIP |
Symbolic CIP driver separately available from Trihedral. |
|
|
Automation Direct |
DL Family of PLCs, Click Family of PLCs, Productivity Family of PLCs |
Modbus |
VTScada driver allows native DL PLC addressing in our Modbus driver (e.g., V2105, C33, etc). |
|
Cisco |
Catalyst 2950 Series Switches |
SNMP |
|
|
Control Microsystems / Schneider |
Telesafe RTU Family, SCADAPack® RTU Family |
Modbus |
Supports to access time stamped data recorded by RTUs using the Data Logger (DL) functions. |
|
SCADAPack® RTU Family Using RealFLO® |
Enron Modbus |
|
|
|
SCADAPack® RTU Family |
DNP3 |
|
|
|
Telesafe RTUs |
DF1 |
|
|
|
CSE Semaphore |
TBox® RTU |
Modbus |
Supports to access time stamped data recorded by RTUs using Sample Tables and Chronologies. |
|
TBox® RTU Family Using TFlo® |
Enron Modbus |
|
|
|
Davicom |
DV-Mini, DV-208, DV-216 |
SNMP |
|
|
Digital Control Company (DCC) ® |
DCC Pump Controllers |
Modbus |
|
|
Eaton |
PW9155 UPS |
SNMP |
|
|
Flygt® |
MultiSmart Pump Controller® |
Modbus |
Previously branded as MultiTrode® MultiSmart. |
|
DNP3 |
|||
|
Foxboro® |
C50 RTU |
DNP3 |
|
|
GE |
D20/D200 RTUs |
DNP3 |
|
|
Modicon / Schneider |
Modicon 984 Family of PLCs, Modicon Compact Family of PLCs, Modicon Quantum Family of PLCs, Modicon TSX Family of PLCs |
Modbus |
|
|
Motorola IP Gateway |
Motorola ACE RTUs |
Motorola® Ace Gateway API |
VTScada supports RTU redundancy within the IP Gateway device. |
|
MPE® |
MPE Duplex Controller |
Modbus |
|
|
Phoenix Contact |
AXC1050 |
IEC-60870-104 |
|
|
Power Measurement Ltd.® |
ION Series Meters |
Modbus |
|
|
ION Series Meters |
DNP3 |
|
|
|
RuggedCom / Siemens |
RX1000 Router |
SNMP |
|
|
Schlumberger® |
Q1000 Meters |
DNP3 |
|
|
Schweitzer Engineering Laboratories, Inc (SEL Inc) |
SEL-2030 Communications Processor |
DNP3 |
|
|
Sixnet® |
Micro-Versa TRAC, Sixnet SixTRAC |
Modbus |
|
|
Surfline 9015 |
9015 |
Modbus |
With firmware feature enabled. |
|
Thermo Fisher Scientific |
AutoPILOT |
Enron Modbus |
|
|
Woodward® |
easYgen Series, EGCP-3, DTSC, DLSC-2, 723 PLUS, 733, 828 |
Modbus |
|
Native VTScada Protocols
Definitions:
DH
Dual homed.
Native Serial
Driver supports native serial communication as defined in protocol standard document(s) on PC serial ports using VTScada "Serial Port" tags
Modem
Driver supports native serial communication as defined in protocol standard document(s) over modems defined in the operating system
Native TCP/IP
Driver supports native TCP/IP communication to devices as defined in the protocol standard document(s)
TCP/IP Tunnel
Driver supports tunnelling of serial protocol via Ethernet-connected TCP/IP to serial converters using VTScada "TCP/IP Port" tags
Native UDP/IP
Driver supports native UDP/IP communication to devices as defined in the protocol standard.
UDP/IP Tunneled
Driver supports tunneling of serial protocol via Ethernet-connected UDP/IP to serial converters using VTScada "UDP/IP Port" tags.
Other Connection
Driver supports device or protocol specific interface or methodology not covered by above definitions (e.g. ODBC).
Virtual PLC
Driver supports VTScada acting as a memory-mapped PLC or RTU that other devices can read from or write to.
| Driver Tag Type | |||||||||||
| Protocol | Example Device | Native Serial | Dial up | ||||||||
| Modem | Native TCP/IP | TCP/IP Tunnel | Native UDP/IP | UDP/IP Tunneled | Connection | Virtual PLC | More Info | ||||
| Allen Bradley DF1 Compatible PLC/RTU | Allen Bradley DF1 | PLC2, PLC3, PLC5, SLC500 | X | X | X | X | DH/DH+ | X | DH/DH+ requires additional interface hardware. | ||
| Supports Virtual PLC in PLC-2 compatible mode only. | |||||||||||
| Allen Bradley PCCC | PLC5, SLC500 | X | |||||||||
| BACnet Driver | BACnet | BACnet Compliant Devices | X | ||||||||
| Bristol BSAP/IBP Driver & Network | Bristol BSAP | Bristol 33xx Series RTUs, ControWave RTUs | X | X | X | X | Separately available from Trihedral. | ||||
| Bristol IBP | Bristol ControWave RTUs | X | |||||||||
| CIP/ENIP Device | Allen Bradley CIP | CompactLogix®, ControlLogix® | X | ||||||||
| Campbell Scientific Array Driver | Campbell Scientific Array Protocol | CR10X and CR510 Data Loggers using array OS | X | X | X | X | |||||
| Campbell Scientific Pakbus Driver | Campbell Scientific Pakbus | CR200, CR800, CR850, CR1000, CR3000, CR5000 Data Loggers | X | X | X | X | X | Security features for native TCP/IP not implemented. | |||
| DDE Client | DDE (Dynamic Data Exchange) | MS Excel | DDE | Can act as DDE Client or Server. | |||||||
| Data Flow Systems RTU | DFS Protocol | Data Flow Systems® RTUs | X | X | X | Also works with DFS NIM. | |||||
| Koyo DirectNET | Direct Net | PLC Direct® DL Family of PLCs | X | X | X | X | |||||
| DNP3 Compatible RTU | DNP 3.0 | DNP 3.0 Compliant Devices | X | X | X | X | X | X | |||
| Enron Modbus RTU | Enron Modbus® | Enron Modbus Compliant Devices | X | X | X | X | X | ||||
| Fisher ROC Driver | Fisher® ROC | ROC800, 800L, FloBoss™ 103, 107 | X | X | X | X | X | ||||
| GE Series 90 Driver | General Electric® SNP, SNPX | GE Series 1 PLC, Series 5 PLC, Series 6 PLC, Series 90 PLC | X | No direct support for use on Ethernet to Serial converters. | |||||||
| General Electric® SRTP | Series 90 PLC, RX3i PLC | X | |||||||||
| IEC 60870-5 Driver | IEC-60870-104 | RTUs & PLCs from Various Manufacturers | X | X | |||||||
| JSON/XML Driver | JSON | JSON Compliant Websites and Devices | X | Supports JSON retrieved over HTTP and HTTPS. | |||||||
| Also supports XML (Read only). | |||||||||||
| Modbus Compatible Device | Modbus ASCII | Modbus ASCII Compliant Devices | X | X | X | X | X | ||||
| Modbus PLUS | Modbus Plus Compliant Devices | Modbus Plus | Modbus PLUS requires additional interface hardware. | ||||||||
| Modbus RTU | Modbus RTU Compliant Devices | X | X | X | X | X | |||||
| Open Modbus/TCP | Open Modbus/TCP Compliant Devices | X | X | X | X | X | x | X | See example devices on page 2. | ||
| Motorola ACE RTU | Modbus, M-OPC, DNP3, IEC | Moscad RTU Family, ACE Family | X | Requires MDLC IP Gateway device. | |||||||
| Motorola IP Gateway | Motorola® Ace Gateway API | Motorola ACE RTUs | X | Supports RTU redundancy within the IP Gateway device. | |||||||
| MQTT Client Driver | MQTT 3.1.1 | X | Subscriber only. Requires 3rd-party MQTT server (a.k.a. Broker) | ||||||||
| NMEA 0183 Driver | NMEA 0183 | Serial GPS | X | X | X | X | Functions as talker and listener. | ||||
| Omron FINS Driver | Omron® FINS | CS Series PLC, CJ Series PLC | X | ||||||||
| Omron Host Link PLC | Omron® Hostlink | C Series PLC, CS Series PLC, CJ Series PLC | X | X | X | X | |||||
| OPC DA Client | OPC® DA Client | OPC Servers for Various Products | OPC | Supports hundreds of 3rd party OPC servers. | |||||||
| OPC UA Client | OPC® UA - TCP - Binary 1.04 | OPC Servers for Various Products | X | X | Doesn't use a Port tag. Port handling is built-in. | ||||||
| Opto22 Mux Driver | Optomux | Opto 22 Analog & Digital I/O Boards | X | X | X | X | Separately available from Trihedral. | ||||
|
Siemens S7 PLC |
Siemens® ISO over TCP |
S7 Series PLCs |
|
|
X |
|
|
|
|
|
|
|
SNMP Managed Device |
Simple Network Management Protocol (SNMP)® |
Standardized Protocol for Thousands of Devices |
|
|
|
|
|
X |
|
|
|
|
SNMP Agent |
SNMP V1 or V2 |
Allows VTScada to Supply Data to a Networked Device |
|
|
|
|
X |
|
|
|
|
|
SQL Data Query Driver |
SQL Data Query (ODBC) |
SQL Databases |
|
|
|
|
|
|
|
|
|
|
Veeder-Root |
Veeder-Root Serial Interface |
TLS-300, TLS-350, and TLS-350R |
X |
X |
X |
X |
|
|
|
|
|